Yellow screen paperless recorder
Overview of Yellow Screen Paperless Recorder BY-XJ-400012 input Yellow Screen Paperless Recorder, capable of inputting signals such as standard curren
Product details

Yellow screen paperless recorder

overview

BY-XJ-4000 12 input yellow screen paperless recorder, capable of inputting signals such as standard current, standard voltage, frequency, millivolts, thermocouples, thermal resistance, etc. It has functions such as sensor isolation distribution output, relay alarm output, transmission output, flow accumulation, temperature and pressure compensation, historical data transfer and storage, printing, and remote communication.

Functional Features

  1. 5.1-inch 160 × 128 dot matrix graphic LCD display with LED backlight.

  2. The screen contrast can be freely adjusted;

  3. High speed, high-performance 32-bit ARM microprocessor, with a screen response time of less than 0.2 seconds, capable of detecting, recording, displaying, and alerting 12 signals simultaneously;

  4. Adopting new large-scale integrated circuits and carefully designed components from internationally renowned factories;

  5. Large capacity FLASH flash memory chips store historical data and never lose data in case of power failure;

  6. Fully isolated input, capable of inputting multiple signals without the need for jumpers, can be configured through software;

  7. The quantity display has a wide range of numerical values and can display 5-digit values: -9999 to 19999;

  8. Support vacuum Scientific notation display;

  9. Chinese Laidan configuration, display project tag number, and engineering unit. The software password lock ensures user configuration security.

  10. Alarm display, indicating the lower and lower limits, lower and upper limits, and upper and upper limits of each channel alarm. Can record the last 15 alarm messages;

  11. Use USB 2.0 interface to transfer and backup historical records, supporting 256MB, 512MB, and 1GB USB drives;

  12. Standard serial communication interfaces: RS-485 and RS-232C;

  13. Supports standard Modbus RTU communication protocol, in addition to our company's ScanX data management software, it also supports popular professional configuration software such as iFIX, Kingview, MCGS, PCAuto, etc., without the need for dedicated drivers;

  14. Can be connected to an external micro printer, supporting manual printing and timed automatic printing, meeting the needs of users for on-site printing;

  15. Integrated hardware real-time clock, the clock can run accurately even in the event of power failure;

  16. The new switch power supply operates normally within the range of 85VAC to 265VAC;

  17. Provide transmitter+24VDC isolated power distribution.

  18. The compensation model is rich and can compensate for various media such as liquids, general gases, steam, and natural gas.

  19. The small flow supplement metering function compensates according to the set value after the instrument loses power.

  20. Provide 8-hour shift reports, 12 hour shift reports, daily reports, and monthly reports. The settlement time can be freely set.

  21. When the temperature sensor or pressure sensor malfunctions, it will automatically switch to the set temperature and pressure to calculate the compensation amount.

  22. It has a power-off recording function, which records the time of instrument power on and power-off, displays the cumulative power-off time, and prevents users from stealing steam during power outages.

  23. The all aluminum sealed shell and internal shielding plate ensure the normal operation of the instrument in harsh environments.

Specification

  • monitor5.1-inch 160 × 128 dot matrix TFT graphic LCD display screen, LED backlight, wide viewing angle

  • Basic error:±0.2%F·S

Fully isolated input: 1-12 channel signal input, fully isolated between channels, isolation voltage>400V

  • Enter specifications

BY-XJ-7000 series input range meter

Input Type

Range of measurement


Input Type

Range (℃)

Type II: 0-10mA, 0-5V

-9999~19999

heat

electricity

image

B

500~1800

Type III: 4-20mA, 1-5V

-9999~19999

S

0~1600

20mA

0~20 mV

K

0~1300

100mV

0~100 mV

E

0~1000

Frequency Fr

0~10KHz

J

0~1000

heat

electricity

Resistance

Cu50

-50~140℃

R

0~1600

Cu53

-50~140℃

N

0~1300

BA1

-100~600℃

T

0~380

BA2

-100~600℃

WRe5-26

0~1800

Pt100

-200~650℃

radiation

pyrometer

F1

700~2000

Resistance 0~350 Ω

-9999~19999

F2

700~2000


  • Output specifications

Distribution: 4 sets of 24VDC output, output current of 60 mA/set, 12 configurable relay contact outputs, contact capacity of 3A, 250VAC (resistive load) default to normally open contacts. *Multiple 4-channel analog output (transmission output or PID output), 4-20mADC, load resistance<600 Ω

  • Compensation operation

Steam: According to the steam density table, query the steam density and compensate for the mass flow rate of steam.

Pressure range 0.1-22MPa, temperature range 0-600 ℃

Water: According to the water density table, query the water density and compensate for the mass flow rate of water

Temperature range 0-150 ℃

  • Cumulative range:0~9999999999

  • Communication and printingCommunication interface: RS232C or RS485

Baud rates: 1200, 2400, 1800, 9600, 19200, 38400, 57600

Printing interface: RS232C directly connected to serial micro printer

  • recording time

Record interval: 1, 2, 5, 10, 15, 30, 60, 120, 240 seconds optional.

Record length: 72 hours/pen (record interval of 1 second) to 720 days/pen (record interval of 4 minutes)

Record Interval

1 second

2 seconds

5 seconds

10 seconds

15 seconds

30 seconds

1 point

2 points

4 points

Record length

72 hours

6 days

15 Days

30 days

45 days

90 days

180 days

360 days

720 days

  • Data backup and transfer256MB~1G USB drive optional

  • Cold end compensation error of thermocouple:± 1℃

  • power-off protectionBuilt in FLASH memory, protects parameters and historical data, and can be saved after power failure. Integrated hardware clock that can operate accurately even after power failure.

  • power supplySwitching power supply 85VAC~265VAC, 50Hz ± 5%, power consumption<59W

  • ambient temperature:0-50℃

  • ambient humidity:0-85%RH