XSD Multi Channel Display Instrument
summary:
XSD multi-channel display instrumentIncrease the number of measurement and display channels to reduce equipment costs,
There are three types: 2-channel, 3-channel, and 4-channel. Basic functions are consistent with XST series
Same (without 8-segment line correction),Independent setting of input signals and ranges for each channel;
Each channel calibration and independent setting of digital filtering.Instrument power supply 220V AC, 24V D
Or 12V DC,Appearance and panel form: 160×Various panel forms or LCD displays of 80.
Technical indicators:
4 Power supply: 220V AC powered instrument: 220V ± 10%, power consumption less than 7VA;24V DCPower supply instrument: 24V ± 10%, power consumption less than 5VA; 12V DCPower supply instrument: 9V~20V, power consumption less than 5VA. Other power specifications are subject to the accompanying manual
4 Working environment: 0 ℃~50 ℃, humidity below 90% R.H Instruments with a wide temperature range should be specified when ordering
4 Display range: -1999~9999, decimal point position can be set, display resolution: 1/10000
4 Input signal types: voltage, current, thermistor, thermocouplemV、 There are 7 types of potentiometers and remote pressure gauges, among which
Voltage: 1V~5V DC, 0V~5V DC can be selected through setting
Current: 4mA~20mA,0mA~10mA,0mA~20mA can be selected through setting
Thermal resistance: Pt100, Cu100, Cu50, BA1, BA2, G53 can be selected through settings
Thermocouples: K, S, R, B, N, E, J, T can be selected by setting
Other input signals or division marks need to be specified when ordering
4 Basic error: less than ± 0.2% F.S
4 Measurement resolution: 1/60000, 16 bit A/D converter
4 Measurement control cycle: channel count x 0.2 seconds
instrument for drawing circles check:160 × 80, 96 × 96, 96 × 48, 72 × 72, etc
Wiring instructions:
4 A. When B and C represent input and resistance signalsWhen receiving other signals
4 NO, COM, NC indicate when the alarm output relay outputsWhen outputting voltage
4 V+, V-Indicate the power supply and polarity of external sensors (transmitters)
4 O+, O-Indicate the transmission output and polarity