This series of instruments has the following characteristics:
·Adopting advanced chip manufacturing technology, simplifying structure, improving product stability and anti-interference ability.
·Using digital correction,Input thermocouple, thermistor, standard signal optional,No zero drift.
·Adopting dual four digit digital display,two101line(Red, green)Light column display,Intuitive and eye-catching,easy to operate,All operation functions only require five keys to complete.
·It can directly replace general dynamic coil and digital display instruments.
·Wide range power supply, adaptability:85V~264VACDC power supply can also be used(24VDC).
·Signal input of any specification,Multiple specifications of signal output.
2、 Main technical parameters
1. Conditions of Use: ambient temperature0~50℃;relative humidity≤90%;supply voltage 85~264V AC,50/60Hz;atmospheric pressure85~106Kpa.
2. Basic error:
·Four digitLEDdisplay:±(0.2%F·S±1character);±(0.5%F·S±1character).
·101 Line light column display:Full scale1%, (applyXMGtype).
3. display resolution:
·Four digitLED: According to the range of measurement,Can be set as0.001、0.01、0.1reach1 four types.
·101 Line light pillar: Full quantity1%, (apply toXMGtype).
4. Input impedance: Thermocouples, voltage signals(greater than500K),thermal resistance(Three leads are equal and less than5short for Europe) ,electricitystreaming signal(less than250short for Europe).
5. output characteristic: Relay contact,Its capacity is220VAC/3Aperhaps24VDC/3A,Pure resistive load. NoneThe capacity of the contact relay is220VAC/1.5A.
6. Temperature range for thermocouple cold junction compensation:0~80℃.
7. analog output:0~l0mAperhaps4~20mA.
8. Communication method:RS485、RS2320.
9. Can be carried24VDCPower Output,Isolation Voltage1000V,Maximum current30mA.
10. Power consumption:4VA.
11. External dimensions(mm):horizontal type160×80×80,Vertical80×I60×80,square96×96×100,horizontal type96×48×l00,Vertical48×96×l00.
12. Dimension(mm): Horizontal153+10×76+10,Vertical76+10×153+10,square92+10×92+10,horizontal type92+10×45+10,Vertical45+10×92+10.
13. weight:make an appointment0.5kg.
IIIInstrument modelAnd lose Enter specifications
1 XMSeries intelligent digital regulator
Example:XM─11117showTwo position control regulator powered by switch power supply, input signal is thermocouple, vertical installation method(80×160mm), canoutput24VDC power supply.
2、XMGSeries Intelligence101lineLight column digital regulator
Example:XM─11224showPowered by switch mode power supplySingle beam of light+Digital display regulator, inputsignaldoThermistor,Horizontal installation method(160×80mm),1~5VTransmission output.
3 Enter specifications(Division number)
4User specific requirements specifications (division)Number)
4、 Instrument function
1. display function
·Normal working condition :
LED:Main screen displays parameter measurement values(PV),Given values for secondary screen display parameters(SV)
beam:Red display of parameter measurement values(CPV) ,Green displays the given value(SV)
·Alarm status :
LED:Main screen displays parameter measurement values(PV),The secondary screen alternately displays the given value(SV)And alarm parameters
code(Upper limit alarm parameterAL-HOr lower limit alarm parameterAL-L).
beam:Red display of parameter measurement values(CPV) ,Green displays the given value(SV)And alarm values(Display two bright bands)
2. Control and alarm functions
·Two position control or single limit alarm
·Three position control or dual limit alarm
·Multi control or multi limit alarm
3. Wire breakage protection function
An alarm can be triggered if the input signal is below the lower limit of the range, exceeds the upper limit of the range, the sensor is disconnected, or the sensor specification is set incorrectly. The instrument will automatically stop control. At this pointLEDSecondary screen flashing displayAL——.
5、 Instrument operation and wiring
There are five buttons on the dashboard
SET—Parameter code selection key , A/M—automatic/Manual switch key, ▲—Incremental key,▼—Reduce key, ?—Decimal point movement key.
1 Division number setting
pressSETkey,When the main screen displaysINSNtime,Press again▲Key or▼key,Secondary screen display division number code(As shown in the table of division number codes below 0 、 1 、 2 ……)
INSNInput parameters (division number)
2、instrumentTerminal connectionlineConfiguration andterminalWiring diagram
XM、XMGSeries instrumentsconnectlineterminalconfiguration
Annotation:horizontal type160×80mm,Vertical80×I60mm..
1 Single display instrument: analog output(mA)The terminal is5+、6-,24VPower OutputThe terminal is10+、11-.
2 Two position instrument: (1)Analog output(mA)The terminal is10+、11-,24VPower OutputThe terminal is9+、8-.
(2)What is the upper or lower limit alarm (or control) terminal5、6.
3 Three position instrument: (1)Analog output(mA)The terminal is10+、11-,24VPower OutputThe terminal is7+、2-.
(2)The lower limit alarm (or control) terminal is5、6What is the upper limit alarm (or control) terminal8、9.
4 Multi position instrument: (1)24VPower OutputThe terminal is7+、2-.
(2)The lower limit alarm (or control) terminal is10、11What is the upper limit alarm (or control) terminal5、6What is the upper limit alarm (or control) terminal8、9.
Annotation:square96×96mm,horizontal type96×48mm,Vertical48×96mm.
1Single display instrument: analog output(mA)The terminal is8+、7-,24VPower OutputThe terminal is13+、14-.
2Two position instrument: (1)Analog output(mA)The terminal is13+、14-,24VPower OutputThe terminal is4+、3-.
(2)What is the lower or upper limit alarm (or control) terminal7、8.
3Three position instrument: (1)Analog output(mA)The terminal is13+、14-,24VPower OutputThe terminal is4+、3-.
(2)The lower limit alarm (or control) terminal is7、8What is the upper limit alarm (or control) terminal1、2.
4Multi position instrument: (1)24VPower OutputThe terminal is7+、2-,24VPower OutputThe terminal is6+、5-.
(2)The lower limit alarm (or control) terminal is3、4What is the upper limit alarm (or control) terminal7、8Upper limit alarm (or control) terminalcorrect1、2.
XM、XMGSeries instrumentsconnectlineterminalWiring diagram(Horizontal shape160×80mmVertical shape80×160mm)
XM、XMGSeries instrumentsconnectlineTerminal Wiring Diagram (Square)96×96mmVertical shape96×48mmHorizontal shape48×96mm)
6、 Ordering Notice
(When placing an order, the instrument structure and additional functional specifications must be specified)
1 Instrument structure form
2 Additional functions of instruments
The instrument can be equipped with additional functions as shown in the model table1—9term
pour:Rectangular structured instruments are slightly different.
(1)Multi control or multi limit alarm instrument,Cannot select additional features.
(2)Three position control or dual limit alarm instrument,Only one specification of additional features can be selected.
(3)Two position control or single limit alarm instrument,Single display, no alarm and control instrument,Two specifications of additional power can be selectedability.
XMIntelligent digital instruments andYIT-150Wiring method when using a differential remote transmission pressure gauge or a shock resistant differential remote transmission pressure gauge in combination:
1XMIntelligent digital single display instrument andYTT—150Wiring when used in conjunction with type:
lReceivingYTT—150Voltage signal of type, XMIntelligent digital instrument terminal1Connect directly2Connect negative.
2 、XMIntelligent digital instrument towardsYTT—150Type provided6The output terminal of the volt power supply is10Connect directly11Connect negative.
3 、XMTerminal of intelligent digital instrument2And terminals11short circuit,Used as a public point.
IIXMIntelligent digital instrument with two digit control or single limit alarmYTT—150Wiring when used in conjunction with type,The relay output normally open contact or normally closed contact terminal is5and6,Other identical ones1、2、3The wiring is the same.
IIIXMIntelligent digital instrument with three digit control or dual limit alarmYIT—150Wiring when used in conjunction with type,The relay output normally open contact or normally closed contact terminal is5and6;8and9Other identical ones1、2、3The wiring is the same.
XMIntelligent digital instrument terminal wiring diagram(Horizontal shape160×80mm,Vertical shape80×160mm)