Characteristics of DJ3S
1. Adopting imported sensors with stable performance
2. High precision and fast response speed
3. On site concentration display
4. SIM card can be installed inside the alarm
5. Use GPRS data transmission method
6. The alarm can store 5 recent alarm response records internally
7. Can set two more phone numbers to receive alarm messages
8. The alarm sends a heartbeat signal to the monitoring platform every half an hour based on real-time environmental concentration
9. Upon detecting alarm data, immediately upload it to the monitoring platform and send a text message to the designated user
Characteristics of DJ3
1. Adopting imported sensors with stable performance
2. High precision and fast response speed
3. Timely alarm on the basis of preventing false alarms
4. On site concentration display
5. Sound and light alarm indication
6. Alarm control output (9V)
Sensor type: flat semiconductor type
Gas detection: methane (natural gas)
Working voltage: AC 220V ± 15%, 50Hz
Power consumption:<2W
Usage environment (indoor type): Temperature: 0 ℃~+55 ℃ Humidity:<93% RH (no condensation)
Storage temperature: -25 ℃ to+55 ℃
Response time:≤30s
Recovery time:<30s
Sampling method: Natural diffusion type
Detection range:0~20%LEL
Alarm setting value:5 %LEL
Basic error: ≤± 3% LEL
Alarm methodSound and light alarm
Alarm volume:≥70dB
Sensor lifespan: 5 years
Output node type: DC12V output
Weight: 210g
External dimensions:(L)130*(B)80*(H)40,(mm)
Product appearance and functional indicators
serial number |
name |
function |
1 |
Green power indicator light |
Power indicator |
2 |
Red alarm indicator light |
alarm indication |
3 |
Yellow fault indicator light |
Fault indication |
4 |
Self check button |
Sound and light function test |
5 |
Concentration display window |
Real time concentration display |
Installation Instructions
1. Installation location: (see Figure 1)
Install the detector at a suitable location within a radius of (2-4) meters from the air source, within a range of 30cm from the ceiling.
#Do not install in high temperature and humid places.
#Do not install it near smoke exhaust pipes or chimneys.
#Try to avoid oil fume and steam pollution as much as possible.
#Avoid installing in windows or passages with high wind speeds.
2. Installation method:
After selecting the installation location, first install the hanging board on the wall, and then fix the detector to the hanging board. The detector should be installed firmly and not tilted. If the wall is a smooth surface such as tiles or glass, the wall at the installation location can be cleaned and fixed using the 3M adhesive in the product packaging; Ordinary walls require drilling holes on the wall and fixing them with plastic expansion bolts.