R500 series RTU
The R500 series RTU is a new generation RTU product from Ankang Technology, which adopts advanced 32-bit processors and real-time operating systems, c
Product details

Product Overview

The R500 series RTU is a new generation RTU product from Ankang Technology, which adopts advanced 32-bit processors and real-time operating systems, combining high performance and real-time performance, with integrated control systems. The R500 series RTUs are not only capable of easily handling routine tasks such as logic operations, timing switches, addition and subtraction counting, but also capable of completing advanced functions such as complex data processing, natural gas metering, high-speed counting, PID control, and communication networking.


Product Features

·Modular structural design, supporting standard DIN rail installation

·The main control integrates Ethernet and serial ports, supporting the use of communication expansion modules to add additional Ethernet or serial ports

·Comprehensive communication services, supporting communication protocols such as Modbus RTU/TCP, DNP3, etc

·IEC 61131-3 standard, supports LD, FBD, ST, SFC, and IL programming

·Support power supply, main control, and network redundancy to ensure high availability operation of the system

·Adapt to harsh working environments, with a temperature range of -40~70 ℃ and a humidity range of 5%~95% RH

·Through CE certification, achieve EMC electromagnetic compatibility level 3 standard


Application field

General Industrial Data Collection and Process Control

Oilfield natural gas processing station, combined station

Oil well process parameter detection and production optimization control in oil fields

Monitoring of oilfield transfer stations, oil depots, and oil production metering stations

Gas lift well control and natural gas flow metering

Monitoring of hot water boilers and industrial steam boilers

Remote control of water source well and pumping station

Pipeline leakage detection, valve control, and pipeline flow measurement

Detection and control of open channels, water gates, and water levels

Atmospheric environment and water quality monitoring

Remote telemetry and control of power system parameters

Automatic control of water supply

Automated control of urban water treatment


Environmental indicators

environmental conditions

working environment

-40 ~ +70℃,5 - 95% RHNo condensation

storage environment

-50 ~ +80

Pollution level

Non corrosive gas

pollution level

2level

overvoltage

2level

Mechanical environment

vibration

5 ~ 16 Hzuniform amplitude1 mm
16 ~ 150 HzConstant acceleration0.5 g

impact

maximum intensity10 g11msHalf sine wave

Protection level

Shell protection

IP 20

Electromagnetic Compatibility

Anti interference level

Bdistrict

Electrostatic discharge anti-interference

IEC61000-4-2

Contact discharge:6 kVAir discharge:8 kV

Radio frequency electromagnetic field radiation anti-interference

IEC61000-4-3

80 MHz ~ 1 GHz 10 V/m

1 kHz 80% AMsine wave

Transient pulse group anti-interference

IEC61000-4-4

Power Supply:2 kVOther:1 kV

Surge immunity

IEC61000-4-5

Power Supply:2 kV CM1 kV DM
Others:
1 kV

Radio frequency field induction conduction anti-interference

IEC61000-4-6

150 kHz ~ 80 MHz10 Vrms
1 kHz 80% AMsine wave

Power frequency magnetic field immunity test

IEC 61000-4-8

30 A/m,Stable and continuous magnetic field test

Conductive emission

IEC 61131-2 Aclass

0.15 MHz ~ 0.5 MHz<79dB (MV)Quasi peak value;<66 dB (MV)average

0.5 MHz ~ 30 MHz<73dB (MV)Quasi peak value;<60 dB (MV)average

radiated emission

IEC 61131-2 Aclass

30 MHz ~ 230 MHz< 40 dB (μV/m)quasi-peak

230 MHz ~ 1 GHz< 47 dB (μV/m)quasi-peak

CPU controller

Module model

CPU-5021 / CPU-5021R

CPU-5051 / CPU5051-R

General Information

sizeW*H*D (mm)

43*118*92

Rated power consumption

5 VDC@700 mA

Calculate and store information

Calculation speed

400 MHz

400 MHz

Power off storage space

128 KB

maximumI/Oinformation

Number of expansion modules

48

48

Digital input

512

512

digital output

512

512

Analog input

256

256

Analog output

128

128

RTDinput

64

64

Ethernet

2*RJ45 100Mbps

serial port

1*RS232 1*RS232 / RS485

Modbus RTU

main site/slave

main site/slave

Modbus TCP

client/server

client/server

PID回路

32

32

Digital input

Module model

DI16-24VDC

DI4-24VDC PULSE

General Information

sizeW x H x Dmm

43*118*92

Rated power consumption

5 VDC@90 mA

5 VDC@110 mA

Digital input

number of channels

16

4

input method

Leakage type

Unipolar pulse

Input voltage range

24 VDC ±10%

5 ~ 24 VDC

Typical input current

5 mA

8 mA

Signal range

signal”1”> 8 VDC

signal0< 3 VDC

amplitude5 ~ 24 VDC

Maximum input frequency

30 Hz

10 kHz

Counting range

-

32 bits

Bus isolation

support

support

Transient protection

support

support

digital output

Module model

DO16-24VDC

General Information

sizeW x H x Dmm

43*118*92

Rated power consumption

5 VDC@95 mA

digital output

number of channels

16

output method

Source type

Output voltage range

24 VDC ±10%

Maximum current of the channel

180 mA

Maximum current at the common end

3 A

Channel leakage current

100 uA

Bus isolation

support

Transient protection

support

Analog input

Module model

AI8-I

AI8-I HART

AI4-RTD

General Information

sizeW x H x Dmm

43*118*92

Rated power consumption

5 VDC@95 mA

5 VDC@80 mA

5 VDC@85 mA

Analog input

number of channels

8

8

4

input method

current

current

thermal resistor

resolution

16 bits

16 bits

16 bits

sampling time

100 ms

100 ms

100 ms

Convert time

10 ms

10 ms

10 ms

Input Range

4 ~ 20 mA

4 ~ 20 mA

PT100

Range of numerical quantities

10000 ~ 50000

measurement accuracy(25℃) *

±0.1% F.S

±0.1% F.S

±0.3% F.S

measurement accuracy(Full scope)*

±0.5% F.S

±0.5% F.S

±0.6% F.S

interference suppression

support

support

support

Bus isolation

support

support

support

Transient protection

support

support

support

HART(Only applicable to)AI8-I HART

HARTversion

HART 5 / HART 7

Supported commands

0-3 / 6-9 / 11-22 / 33 / 35 / 38 / 40 / 44 / 48 / 54 / 59

* ForAI8-I HARTModule, measurement accuracy is not includedHARTDuring communication

Analog output

Module model

AO4-I

General Information

sizeW x H x Dmm

43*118*92

Rated power consumption

5 VDC@100 mA

Analog output

number of channels

4

output method

current

resolution

16 bits

response time

100 ms

output range

4 ~ 20 mA

Range of numerical quantities

10000 ~ 50000

Measurement accuracy(25℃

±0.3% F.S

Measurement accuracy (full range)

±0.5% F.S

Bus isolation

support

Transient protection

support



modelBlock type

modelblockname

functiondescription

power module

PS-15W 24VDC

power module24VDCInput,5VDC 3A

PS-135W 220VAC

85280VACInput,24VDC/5A,5VDC/3Aoutput

Main control module

CPU-5021

Main control module2*RJ45 1*RS232 1*RS232/485

CPU-5021R

Redundant main control module2RJ45 1RS232 1RS232/485

CPU-5051

Main control module2*RJ45 1*RS232 1*RS232/485

CPU-5051R

Redundant main control module2*RJ45 1*RS232 1*RS232/485

communication module

CM-3RS

communication module2*RS232/RS485 1*RS485

CM-2ETH2RS

Network communication module2*RJ45 1*RS232 1*RS232/485

CM-8RS

8 roadRS485communication module

I/Omodule

AI8-I

8 Channel analog input module (current type)

AI8-I HART

8 Channel analog input module (current type, supportsHART

AI4-RTD

4 Channel thermistor module

AO4-I

4 Channel analog output module (current type)

AO4-I HART*

4 Channel analog output module (current type, supports)HART

DI16-24VDC

16 Channel digital input module (leakage type)

DO16-24VDC

16 Channel digital output module (source type)

DI4-24VDC PULSE

4 Channel digital input module (pulse type)

Traffic calculation module

ME-GAS CPU

Dual natural gas flow calculation module

ME-GAS IO

Calculation of dual natural gas flow rateIOmodule

ME-GAS MB

Natural gas flow computer base

Base module

MB-IO

I/OModule base

MB-CPU

Main control module base

MB-2CPU

Redundant main control module base

MB-PS

Power module base

MB-2PS

Redundant power module base

MB-3RS

3 Base of Road Serial Communication Module

MB-2ETH2RS

2 Road Ethernet and2 Base of Road Serial Communication Module

MB-8RS

8 roadRS485Communication module base

Bus cable

E-BUS5A-0.5

E50Bus connection cableA0.5m, with two end plugs)

E-BUS5A-1.0

E50Bus connection cableA1.0m, with two end plugs)

E-BUS5A-2.0

E50Bus connection cableA2.0m, with two end plugs)

E-BUS5A-3.0

E50Bus connection cableA3.0m, with two end plugs)

E-BUS5B-0.5

E50Bus connection cableB0.5m, with two end plugs)

E-BUS5B-1.0

E50Bus connection cableB1.0m, with two end plugs)

E-BUS5B-2.0

E50Bus connection cableB2.0m, with two end plugs)

E-BUS5B-3.0

E50Bus connection cableB3.0m, with two end plugs)

* AO4-I HARTThe module is currently under development and has not been launched yet


Gas transmission station

微信截图_20240731121900.png

CPU-5021 is the main control module, which collects and processes data from various I/O modules. The upper computer system reads various working condition data on site through the network for display, alarm, and analysis;

CM-3RS is a serial communication expansion module used to connect various serial devices. In this example, data from ultrasonic flow meters and gas component analyzers are obtained through Modbus protocol;

ME-GAS CPU is a natural gas flow calculation module that calculates, accumulates, and saves the flow rate of natural gas orifice plates based on industry standards for use in the main control program;

Various I/O modules perform corresponding automatic control based on hardware configuration and application programs, such as PID regulation, pressure and temperature acquisition, switch valve control, etc.



Boiler control

图片5.png


The AI8-I analog input module is connected to corresponding sensors for temperature, liquid level, pressure, oxygen content, flow rate, etc. It collects process data at high speed with a resolution of 16 bits and a cycle of 100 us, such as return water/supply water/inlet water/outlet temperature and pressure, blower outlet air pressure, furnace outlet pressure, flue gas oxygen content, etc;

CPU-5051 supports PID algorithm to adjust the output of the burner in real-time and maintain stable internal temperature of the boiler; Maximum support for 32 circuits, powerful computing power support, allowing real-time adjustment of the main circuit (steam temperature), secondary circuit (combustion air/fuel ratio), and even more circuits to ensure efficient combustion;

DO16/AO4 output module controls fuel valves, feedwater pumps, blowers, induced draft fans, etc. based on current liquid level, flow rate, pressure, etc;

Good environmental adaptability ensures stable operation of the system even under complex working conditions such as high temperature and humidity, providing safety protection for system operation. In case of abnormal conditions such as overheating, low water level, overpressure, etc., the burner can be immediately turned off, fuel supply can be cut off, safety valves can be activated, or emergency pressure relief can be implemented to prevent accidents from occurring.



Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!