1.2. Stability: 6 months, ± 0.1% URL
1.3. Environmental temperature impact Zero point error: ± 0.2% URL/56 ℃ Overall error: ± (0.2% URL+0.18% calibration range)/56 ℃
1.4. Vibration impact: In any axial direction, the vibration effect at 200Hz is ± 0.05% URL/g
1.5. Power supply impact: Less than ± 0.005% output range/volt.
1.6. Load impact: There is no load impact unless there is a change in the power supply voltage.
1.7. Electromagnetic interference/radio frequency interference (EMI/RFI impact) When the field strength reaches 30V/M from 20 to 1000MHz, the output drift is less than ± 0.1% of the range.
1.8. Installation location impact When the liquid level diaphragm is installed vertically, the zero drift is at most ± 0.25kPa. When installing the liquid level membrane horizontally, the zero drift is at most 1.25 kPa plus the extension length of the protruding part. All zero drift can be corrected without affecting the range.
2. Functional specifications 2.1. Measurement range:Refer to the selection table
2.2. Zero point and range It can be adjusted using the local range and zero buttons, or remotely using a HART controller
2.3. Zero point positive and negative transfer When zero point negative shift occurs, the lower limit of the range must be greater than or equal to - URL; When zero point is shifted forward, the upper limit of the range must be less than or equal to+URL. The inspection range must be greater than or equal to the measurement range.
|
|
2.4. output 4~20mA DC, Users can choose linear or square root output, digital process variables Overlayed on a 4-20mA DC signal, it can be used by upper level computers using the HART protocol
2.5. Damping time constant The time constant is adjustable, increasing by 0.1 seconds from 16.0 seconds.
2.6. Environmental temperature limit Without LCD meter head: -40 to 85 ℃ Equipped with LCD meter head: -30 to 60 ℃
2.7 . Process temperature limit Silicone oil filling: -40 to 104 ℃ Fill with inert liquid: -18 to 85 ℃ high-voltage side Ordinary silicone oil -40 to 104 ℃ High temperature silicone oil 15 to 315 ℃ Fluorine oil -45 to 205 ℃ Inert liquid -18 to 177 ℃
2.8. Storage temperature limit Without LCD meter head: -46 to 110 ℃ Equipped with LCD meter head: -40 to 70 ℃
2.9. ambient humidity 0-100% relative humidity
2.10. Rated pressure limit of liquid level flange
| standard |
Grade (lb) |
carbon steel |
stainless steel |
| ANSI |
150 |
196MPa |
196MPa |
| ANSI |
300 |
510MPa |
496MPa |
|