HS-6630 SF6 Purity Meter
The SF6 gas purity analyzer is based on measuring the SF6 gas purity of SF6 air or SF6/N2 mixed gas. Widely used for SF6 gas quality testing in SF6 circuit breakers and SF6 composite electrical appliances in power systems; It can also be used in applications where there are several background gases present (with special requirements). The analyzer has a battery charging indicator light and a built-in charger. The detection component can quickly and accurately measure the purity of SF6, and in general, its lifespan can reach ten years.
Main Features
1. Long life detection component.
2. High degree and good repeatability.
3. Built in pressure regulator valve and electronic mass flow meter.
4. Large LCD display.
5. Portable and easy to operate.
6. AC/DC dual-use, built-in rechargeable battery.
7. Fast response, almost no preheating waiting, low gas consumption.
8. The measurement results are not affected by the ambient temperature.
Main technical parameters
Subject |
HS-6630 |
HS-6630A |
measurement range |
0~1 |
0~1 |
Accuracy |
±0.005FS |
±0.004FS |
response time |
0.9 30S |
0.9 15S |
Operating Temperature |
-30℃~50℃ |
-30℃~60℃ |
sensor type |
The first generation low-power thermal conductivity sensor with temperature compensation |
Second generation low-power thermal conductivity sensor with temperature compensation |
storage capacity |
50 items |
70 articles |
working power supply |
Dual use of AC and DC, the battery can work continuously for several hours |
Dual use of AC and DC, the battery can work continuously for several hours |
Sample gas flow rate |
0.5~0.9L/min |
0.5~0.9L/min |
work pressure |
〈1.0MPa |
〈1.0MPa |
display mode |
LCD Chinese |
LCD Chinese |
Data software |
have |
have |
communication interface |
USB1.1 |
USB1.1 |
intake pipe |
Imported Teflon tubing |
Imported Teflon tubing |
intake port |
French Leclery self sealing quick plug interface |
French Leclery self sealing quick plug interface |