Equipped with 485 communication type paper recorder
Overview of 485 Communication Type Paper Recorder 1. With a unique thermal printing recording method and advanced microprocessor control technology, t
Product details
Equipped with 485 communication type paper recorder

1. The paper recorder with 485 communication achieves unparalleled high recording clarity, high precision, high reliability, multifunctionality, and ease of operation through its unique thermal printing recording method and advanced microprocessor control technology. Can be continuously recorded and digitally printed.
2. Each channel of the paper recorder with 485 communication can directly select and receive multiple thermocouple, thermistor, voltage, and current signals, and can digitally display, trend, and record the measured signals. It can simultaneously record the scale value, time, and curve of each signal on a 100mm wide paper grid printed by itself, and print the channel number next to the trajectory of each channel. The measurement signal type, decimal point position, display range, recording boundary, alarm value, hysteresis, system error correction, recording ruler, data printing interval, paper feed speed, printing depth and time parameters can be set through the keyboard, and the set parameters can be protected. The paper recorder with 485 communication is widely used in industries such as medicine, petroleum, chemical, metallurgy, power, and scientific research institutions.
2、 Main performance and technical indicators of paper recorder with 485 communication type
1. Input channel: (1) Single point, double point, three-point, four point, five point, six point, eight point
(2) The type of measurement signal for each channel can be set by the user themselves
2. Channel isolation: (1) Input channels are isolated from each other without interference.
3. Display function: (2) Fixed point or cyclic display of measured values
(3) Set parameter display
(4) Alarm prompt and indicator light
(5) Time display [when all input signals are turned off]
4. Recording function: (1) Adopting imported fixed thermal head, no ink consumption, no pen position error, anti vibration
(2) There are 800 hot stamping points within a range of 100mm
(3) Trend and numerical recording of measured values
(4) Print the ruler scale and each channel mark while recording the curve
(5) Print the scale value, current time, and paper feed speed every 100mm
5. Real time: (1) Set the current date and time through the keyboard
(2) Even if there is a power outage, it does not affect normal timing
6. Curve migration function: By setting the recording boundary, the trend recording curves of different channels can be separated.
7. Scale transformation function: For voltage and current input signals, linear scale of the input signal can be displayed and recorded by setting the display range. The display range of thermocouple and thermistor signals is their measurement range.
8. Input signal type and measurement range: Various thermocouples, thermistors, standard voltage and current signals, set and selected by the keyboard.
Signal type | Range code | measuring range | |
electricity flow |
mA | 01 | 0~10mA |
mA | 02 | 4~20mA | |
electricity press |
mV | 11 | 0~20mV |
mV | 12 | 0~50mV | |
mV | 13 | 0~100mV | |
V | 14 | 0~5V | |
V | 15 | 1~5V | |
heat electricity Resistance |
Pt100 | 21 | -199.9~550.0 °C |
Cu100 | 22 | -50.0~150.0 °C | |
Cu50 | 23 | -50.0~150.0 °C | |
heat electricity image |
T | 31 | 0.0~400.0 °C |
E | 32 | 0~1000 °C | |
K | 33 | 0~1300 °C | |
S | 34 | 0~1750 °C | |
B | 35 | 500~1800 °C | |
R | 36 | 0~1750 °C | |
J | 37 | 0~1250 °C | |
N | 38 | 0~1300 °C | |
Close the channel | 00 | This channel is closed |
9. Paper feed speed: Set freely through the keyboard, with a paper feed speed ranging from 10 mm/h to 990mm/h.
10. Alarm function: (1) Each channel alarm can select upper limit, lower limit, difference upper limit, and difference lower limit
(2) The alarm hysteresis of each channel can be set, and there is an indicator light to prompt when the relay is activated
(3) Relay contact capacity: 24VDC, 3A; 220VAC, 3A
11. Communication: Can provide RS232C or RS485 communication interfaces
12. Analog output: Can provide two 4-20 mA analog transmission outputs
13. Sampling period: 0.6S
14. Digital display and alarm accuracy: 0.2% F.S
15. Trend recording accuracy: 0.2%
16. Digital recording accuracy: 0.2%F.S
17. Input impedance: greater than 10M Ω
18. Power consumption: not exceeding 30W
19. Normal working environment: Temperature range: 0-50 ℃; Humidity range: 10-85%
20. Power supply voltage: 220V 50Hz
21. Dimensions: 144 × 144 × 200mm
22. Hole size: 138 × 138mm
3、 Wiring method for paper recorders with 485 communication

1. Communication interface RS232 connected to TXD connected to 1, RXD connected to 2, GND connected to 3.

2. Communication interface RS485 connected to terminals 1 and 2