Cross flow hot water boiler (vertical)
application area
Product details

Cross flow hot water boiler (vertical)

2020-07-11

application area

Suitable for small businesses, villas and other small and medium-sized areas, it is a ready to use heating system with high efficiency and fast heating speed.

sketch
(1) Long lifespan: The fully immersed working mode of the water pipe overcomes the problem of overheating and damage to the upper part of the smoke tube in the smoke tube boiler;
(2) High efficiency: The flue gas has a three return structure, and the flue gas flows horizontally through the water pipe, which improves the thermal efficiency. A condenser can be installed to enhance the boiler's thermal efficiency;
(3) This series of boilers belongs to low nitrogen, energy-saving, and environmentally friendly boilers with low emissions;
(4) Unique design for good water circulation;
(5) This product has a small water volume and fast heating, and can reach the heating state in 3-7 minutes;
(6) Thermal efficiency of 94-96% or above;

DESCRIPTION
The CLSS series DC hot water boiler adopts a water pipe structure. This series of boilers has a compact and reasonable structure, a long operating cycle, and easy installation, maintenance, and operation. Equipped with Italian brand burners and boilers that are fully matched, different brands of combustion engines that meet design requirements can be selected according to supply and demand, and user requirements. Fully automatic program control and interlock protection have high automation and thermal efficiency, meeting user requirements.

Structural characteristics
1) The burner adopts a top burning type, where the flame extends from the top downwards and fully unfolds. The flame process is long and fully burned, and the flue gas undergoes heat transfer through a circular return path. The high flow rate and long process greatly reduce the exhaust gas temperature and improve thermal efficiency. By accelerating the flow rate of the flue gas, the heat absorption capacity is increased, while ensuring the self-cleaning effect of not adhering to cigarette ash.
2) There is sufficient combustion space, high furnace heat intensity, internal radiation tubes and water-cooled walls can effectively absorb radiation heat, and the heat flux intensity of the heating surface is strong.
3) The flue gas is overcome by the back pressure of the combustion engine and discharged into the atmosphere through the chimney. The boiler exhaust gas emissions meet environmental protection requirements.

Technical parameters of vertical fuel gas water pipe hot water boiler Reserve the right to redefine or modify product information (including appearance, technology, internal structure, etc.) without prior notice
project Rated thermal power Rated supply/return water temperature ℃ Effective water volume m ³ Heating area m ³ Hot water volume m ³/h △ Ⅰ 25 ℃ Thermal efficiency% Diesel consumption kg/h Natural gas consumption Nm ³/h Gas consumption Nm ³/h Power supply V/Hz Supply/return water inlet mm Atmospheric vent mm Discharge outlet mm Chimney mm size weight
model 10000 kcal/h MW Long L Width W High H kg
CLSS0.7-85/70 60 0.7 85/70 0.8 7500 24000
Configure condenser
Over 98%
No condenser configured
94%
-
96%
59.7 71.2 161.1 380/50 DN80 DN40 φ325 1360 1650 2460 2378
CLSS1.05-85/70 90 1.05 1.0 11250 36000 89.6
106.8 241.7 DN125 DN100 DN40 φ325 1580 1860 2660 4156
CLSS 1.4-85/70 120 1.4 1.4 15000 48000 119.5 142.4 322.2 DN150 DN125 DN50 φ325 1800 2080 2860 5230
CLSS1.75-85/70 150 1.75 1.8 18750 60000 149.4 178.0 402.8 DN200 DN150 DN50 φ400 2030 2300 3160 6018
CLSS2.1 -85/70 180 2.1 2.4 22500 72000 179.2 213.6 483.4 DN200 DN150 DN50 φ400 2260 2540 3360 6824
CLSS2.8 -85/70 240 2.8 3.0 30000 96000 239.0 284.8 644.5 DN200 DN200 DN50 φ400 2500 2800 3560 7230

1. The calorific value of fuel is calculated according to the following standards: diesel calorific value of 42900 KJ/kg (i.e. 10248 kcal/kg), natural gas calorific value of 36000 KJ/Nm ³ (i.e. 8600 kcal/Nm ³), and city gas calorific value of 16000 KJ/Nm ³ (i.e. 3800 kcal/Nm ³)
2. If the gas source is coal gas, please provide the calorific value of the gas, the range of gas supply pressure, and altitude when placing an order.
3. The fuel consumption is the consumption at full load of the boiler, and the actual consumption will vary depending on the operating conditions.


Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!