Air quality detector,Atmospheric Environment Monitoring Systemused forGrid based point measurement
ONETEST-108AQL
In response to the "Thirteenth Five Year Plan for Environmental Monitoring Quality Management" issued by the Ministry of Environmental Protection, we will deepen the implementation of the "Air Pollution Prevention and Control Industry Plan", strengthen regional air pollution prevention and control management, and achieveWith the goal of "no blank monitoring, no difference in comparison, one network, one database, one platform", Wanyi Technology has successfully developed the ONETEST 108AQL atmospheric monitoring system by utilizing years of experience in gas detector production, breaking through multiple technical barriers in China, and combining with IoT data platformsAtmospheric Environment Monitoring System.
Atmospheric Environment Monitoring SystemDetecting parameters not onlyIt can cover meteorological indicators such as environmental temperature and humidity, air pressure, wind speed, wind direction, rainfall, and lighting, as well as detect indicators such as ambient airSO2、NO2、O3、CO、CO2、TVOC、PM2.5、PM10、TSP、 Content of negative oxygen ions, etc. The equipment has the characteristics of being compact and sturdy, and includes multiple brick technology. It fully considers the factors of detection drift, zero point correction, and temperature and humidity to ensure stable operation of the equipment in a wider range of fields.
Atmospheric Environment Monitoring SystemONETEST-108AQLMain features of the equipment:
1) Brick products, reliable quality, suitable for grid monitoring and early warning;
2) Highly integrated, enabling synchronous detection of over 10 environmental parameters on a single device, with stable performance and high resolution;
3) Modular product design, convenient for later maintenance;
4) The sampling method for detecting environmental protection related parameters is completely based onAutomated methods for ambient air quality monitoring(HJT193-2005), The equipment comes with a small zero setting device, ensuring accurate and reliable data;
5) 6 optional gas indicators, including gasParameters such as elephant five parameters and noise can be flexibly customized;
6) The equipment has the ability to autonomously regulate temperature, humidity, and pressure, greatly improving environmental adaptability and effectively enhancing the stability and reliability of sensor operation;
7)The circuit design has secondary lightning protection and anti-static capabilities. Meet national standards and resist high-intensity pulse surge current impact. It has anti reverse connection function. conform toEMI and EMC standards.
8) The device has built-in SD card storage function, supporting real-time storage, timed storage, or only storing alarm concentration data;
9) Double layered protective box design ensures safety and security
10) Built in wireless network card, can transmit data remotely through GRPS, or display it locally on the LED screen through RS232
11) ONETEST-108AQL adopts a vertical pole fixing method or a wall mounted fixing method, which is convenient for various outdoor applicationsEnvironmental installation. Optional outdoor optionLED display screen, displaying real-time monitoring values for easy viewing.
Partial installation cases in recent years
Atmospheric environment monitoring systemONETEST-108AQLworking principle:
The sensors and analyzers inside the device transmit multiple test signals in sequence through the interface protocol into the wireless communication node deviceThe independent (DTU) transmission channel of DVR is input to the data collector in the unit after lightning protection treatment; The collector transmits the collected data to the atmospheric monitoring platform system through a wireless data transmission terminal and a TCP/IP network; The system receives and stores monitoring data uploaded by sub stations in accordance with the "National Air Monitoring Network Station Monitoring Data Submission and Transmission Protocol"; Analyze, store, process, review, and upload the received data, and promptly display graphics and analyze data on the platform.
Atmospheric Environment Monitoring SystemONETEST-108AQLDetection parametersoptional
Gas indicators |
chemical formula |
range |
resolution |
Technical principles |
error |
response time |
carbon monoxide |
CO |
0-20PPM |
0.01PPM |
electrochemistry |
±5%F.S. |
≤30S |
nitrogen dioxide |
NO2 |
0-10PPM |
0.001PPM |
electrochemistry |
±5%F.S. |
≤30S |
sulfur dioxide |
SO2 |
0-1PPM |
0.001PPM |
electrochemistry |
±5%F.S. |
≤30S |
ozone |
O3 |
0-1PPM |
0.001PPM |
electrochemistry |
±5%F.S. |
≤30S |
inhalable particles |
PM2.5 |
0-1000ug/m3 |
1ug/m3 |
Principles of Optics |
±5%F.S. |
≤30S |
inhalable particles |
PM10 |
0-2000ug/m3 |
1ug/m3 |
Principles of Optics |
±5%F.S. |
≤30S |
Fugitive dust |
TSP |
0-20.00mg/m3 |
0.01mg/m3 |
Principle of Light Scattering |
±10%F.S. |
≤30S |
Volatile Organic Compounds |
VOC |
0-20PPM |
0.001PPM |
PID |
±5%F.S. |
≤30S |
TVOC |
TVOC |
0-20PPM |
0.001PPM |
PID |
±5%F.S. |
≤30S |
Nitrogen oxides |
NOX |
0-10PPM |
0.001PPM |
electrochemistry |
±5%F.S. |
≤30S |
ammonia |
NH3 |
0-50PPM |
0.01PPM |
electrochemistry |
±5%F.S. |
≤30S |
hydrogen sulfide |
H2S |
0-10PPM |
0.01PPM |
electrochemistry |
±5%F.S. |
≤30S |
methyl mercaptan |
CH4S |
0-10PPM |
0.01PPM |
electrochemistry |
±5%F.S. |
≤30S |
Methyl sulfide |
C2H6S |
0-10PPM |
0.01PPM |
electrochemistry |
±5%F.S. |
≤30S |
**Amine |
C3H9N |
0-10PPM |
0.001PPM |
PID |
±5%F.S. |
≤30S |
carbon disulfide |
CS2 |
0-20PPM |
0.01PPM |
electrochemistry |
±5%F.S. |
≤30S |
STYRENE |
C8H8 |
0-20PPM |
0.001PPM |
PID |
±5%F.S. |
≤30S |
wind speed |
- |
0~70m/s |
0.1m/s |
- |
±5%F.S. |
≤5S |
wind direction |
- |
0~360° |
≤0.5m/s |
- |
±5%F.S. |
≤5S |
temperature |
- |
-40~80℃ |
0.1℃ |
|
≤±0.5℃ |
|
humidity |
- |
0~100%RH |
0.1% |
|
≤±2%RH |
|
air pressure |
- |
10~1100hPa |
0.1hPa |
- |
±5%F.S. |
≤1S |
illuminance |
- |
0~200000lux |
|
- |
±5%F.S. |
≤1S |
rainfall |
|
0-8mm/min |
0.2 mm/min |
|
±4% |
|
noise |
- |
30~130dB |
0.1dB |
- |
±5%F.S. |
≤5S |
Other parameters are availablePlease consult us for your selection…… |
environmentAir Quality Monitoring CloudPlatform Introduction
The software monitoring platform enables cloud access, which can be achieved throughPC、 It can also generate alarm push, which is very convenient to use.
1. Login interface
2. Home Page

3. Map page

4. Real time data display page


6. Data Download
About Wanyi Technology