AT-WSK-DS temperature controller with adjustable temperature rise
◆overview
The AT-WSK-D series products are an automated industrial instrument for controlling ambient temperature, which monitors changes in the measured ambient temperature in a timely manner. When the ambient temperature is ≤ the set value, the controller drives the heating load to work; When the ambient temperature is 3-6 ℃ higher than the set temperature, the controller stops the load operation. By cycling in this way, the temperature of the tested environment can be controlled within the set temperature range.
◆TECHNICAL INDEX
1. Working power supply: AC220V ± 10%, 50Hz/60Hz;
2. Operating environment: temperature -25 ℃~+70 ℃, relative humidity ≤ 95% RH;
3. Temperature control point range: -30 ℃~+70 ℃, accuracy ± 1 ℃, hysteresis of 6 ℃;
4. Output contact: resistive AC220V/5A (normally open, active);
5. Power consumption: ≤ 2W;
6. Insulation resistance: not less than 100M Ω;
7. Vibration resistance: 20m/s210~150Hz works normally;
8. Installation methods: embedded and pedestal type;
9. Dimensions: 48 × 48 × 90 (mm)3);
10. Hole size: 45+0.5×45+0.5.
◆External dimensions
◆ELECTRICAL WIRING
AT-WSK-DJ cooling adjustable temperature controller
◆overview
This series of products is an automated industrial instrument for controlling environmental temperature, which monitors changes in the measured environmental temperature in a timely manner. When the environmental temperature is greater than or equal to the set value, the controller drives the cooling load to work; When the ambient temperature is 3-6 ℃ lower than the set temperature, the controller stops the load operation. By cycling in this way, the temperature of the tested environment can be controlled within the set temperature range.
◆TECHNICAL INDEX
1. Working power supply: AC220V ± 10%, 50Hz/60Hz;
2. Operating environment: temperature -25 ℃~+70 ℃, relative humidity ≤ 95% RH;
3. Temperature control point range: 0 ℃~95 ℃, accuracy ± 1 ℃, hysteresis of 6 ℃;
4. Output contact: resistive AC220V/5A (normally open, active);
5. Power consumption: ≤ 2W;
6. Insulation resistance: not less than 100M Ω;
7. Vibration resistance: 20m/s210~150Hz works normally;
8. Three prevention (TH): prevent damage from gases containing acid, alkali, and salt;
9. Dimensions: 48 × 48 × 90 (mm)3);
10. Hole size: 45+0.5×45+0.5.
◆ELECTRICAL WIRING