ZSXF-D Wet Alarm Valve Productpurpose】
The ZSXF-D wet alarm valve device, along with pressure switches, water flow indicators, sprinkler heads, signal butterfly valves, end water testing devices, sprinkler pumps, etc., constitute the ZS series wet automatic sprinkler fire extinguishing system, which is currently widely used as an automatic sprinkler fire extinguishing system.
ZSXF-D Wet Alarm Valve Product Features
ZSXF-D wet alarm valve is a one-way valve that only allows water to flow into the sprinkler system in one direction and alarms at a specified flow rate. Used for wet fire extinguishing systems filled with water in the pipeline network, the system is in standby mode for a long time, and the pipeline network is filled with pressurized water. When a fire occurs in a certain area within the protected zone, one or more nozzles work, and this valve automatically opens to allow water to continuously flow towards the fire area. Simultaneously activate the hydraulic alarm bell, and the pressure switch emits an alarm signal.
ZSXF-D wet alarm valve
ZSXF-D Wet Alarm Valve Performance Parameters
Model specifications |
ZSFZ100 |
ZSFZ125 |
ZSFZ150 |
ZSFZ200 |
Nominal diameter (mm) |
DN100 |
DN125 |
DN150 |
DN200 |
Rated working pressure (MPa) |
1.2 |
|||
Strength test pressure (MPa) |
4.8 |
|||
Action flow rate (L/min) |
15<Q<60 |
|||
Delay time (s) |
5<t<90 |
|||
Friction (MPa) |
<0.02 |
|||
Alarm Bell Loudness (DBCA) |
>80 |
【ZSXF-D wet alarm valveAppearance and connection dimensions
PRODUCT MODEL
|
Nominal Diameter
(mm)
|
Connection related parameters
|
Dimensions (mm)
|
|||
Number of bolts
|
Bolt specification
|
Center distance of flange screw hole mm
|
A
|
B
|
||
ZSXF-D-80
|
80
|
4
|
M16
|
Φ145
|
250
|
280
|
ZSXF-D-100
|
100
|
8
|
M16
|
Φ180
|
270
|
600
|
ZSXF-D-150
|
150
|
8
|
M20
|
Φ240
|
365
|
665
|
ZSXF-D-200
|
200
|
12
|
M20
|
Φ295
|
465
|
730
|
【ZSXF-D wet alarm valveStructural image