Overview of Electric Three way Regulating Valve
The ZDLQ and ZDLX series electronic electric three-way regulating valves are composed of 3610L series electronic electric actuators and three-way regulating mechanisms. The electric actuator has a servo system inside, which does not require additional servo amplifiers. It has input signals and power to control operation, and the wiring is simple. The regulating mechanism has two modes of operation: merging and diverging. In some cases, it can replace two two-way valves and one three-way pipe and be widely used. Commonly used for two-phase regulation and simple proportioning adjustment in heat exchangers.
Main technical parameters of electric three-way regulating valve
Nominal Diameter |
25 |
32 |
40 |
50 |
65 |
80 |
100 |
125 |
150 |
200 |
250 |
300 |
Valve seat diameter mm |
25 |
32 |
40 |
50 |
65 |
80 |
100 |
125 |
150 |
200 |
250 |
300 |
Rated KV |
8.5 |
13 |
21 |
34 |
53 |
85 |
135 |
210 |
340 |
535 |
800 |
1280 |
Nominal pressure (MPa) |
1.6, 2.5, 4.0, 6.4 |
|||||||||||
Travel distance (mm) |
16 |
25 |
40 |
60 |
100 |
|||||||
Equipped with electric execution Institution model |
361LSA-20 |
361LSB-30 |
361LSB-50 |
361LSB-65 |
361LSB-99 |
|||||||
Enter the multiplier number |
4-20mADC、1-5VDC |
|||||||||||
power supply |
AC220V 50HZ |
|||||||||||
Inherent flow characteristics |
Linear, equal percentage, fast opening |
|||||||||||
Inherent modulation ratio |
30:1 |
|||||||||||
Leakage level |
IV |
|||||||||||
Flange size |
Compliant with JB/79.1 (2) -94, HG20592-97, GB, ANSI, JIS, DIN and other standards |
|||||||||||
body material |
WCB、304、316、WC6、 Titanium, nickel, Hastelloy, Monel, etc |
|||||||||||
Valve core material |
304, 316, 420, titanium, nickel, Hastelloy, Monel, etc |
|||||||||||
Working temperature ℃ |
-40~230 |
|||||||||||
Series type |
Room temperature type, medium temperature type, corrugated pipe sealing type |
Note: The three-way regulating valve produced by our company has a diameter of DN400
Basic structure of electric three-way regulating valve
Serial Number |
name |
call |
1 |
connect |
pipe |
2 |
valve |
body |
3 |
valve |
rush pith |
4 |
valve |
seat |
5 |
valve |
pole |
6 |
valve |
cover |
7 |
fill |
material |
8 |
Packing gland |
|
9 |
actuator |
Technical parameters of electric three-way regulating valve:
model |
Rated output force |
Speed mm/s |
Technical Parameter |
||||
PSL |
361L |
PSL |
361L |
PSL |
361L |
PSL |
361L |
201 |
361LSA-08 361LXA-08 |
1000 |
800 800 |
0.25 |
4.2 4.2 |
Power Supply; AC220V 50HZ Input signal: DC4-20mA DC1-5V (Shielded wire for signal line) Output signal: DC4-20mA Protection level: IP67 With handwheel |
Power supply: AC220V 50Hz Input signal: DC4-20mA DC1-5V (Shielded wire for signal line) Output signal: DC4~20mA Protection level: IP65 Explosion proof mark Exd ll With handle |
202 |
361LSA-20 361LXA-20 |
2000 |
0.50 |
2.1 2.1 |
|||
204 |
361LSA-30 361LXA-30 |
4500 |
0.50 |
3.5 3.5 |
|||
208 |
361LSA-50 361LXA-50 |
8000 |
1.00 |
1.7 1.7 |
|||
312 |
361LSC-65 |
12000 |
6500 |
0.60 |
2.8 |
||
320 |
361LSC-99 |
20000 |
10000 |
1.0 |
2.0 |
Note: Other optional electric actuators: Yangzhou Siemens, UK Rotork, etc
Performance indicators of electric three-way regulating valve
project |
Indicator value |
||
Basic error% |
Equipped with 361L ± 2.5;; Equipped with PSL ± 1.0 |
||
Return difference% |
Equipped with 361L ± 2.0;; Equipped with PSL 1.0 |
||
Dead zone% |
Equipped with 361L ± 3.0 and PSL 1.0 |
||
Constant point deviation% |
teletransmission |
Starting point |
±2.5 |
End |
±2.5 |
||
Electricity off |
Starting point |
±2.5 |
|
End |
±2.5 |
||
Adjustable range |
50: 1 |
||
Rated travel deviation% |
+2.5 |
||
leakage rate |
Compliant with JB/T7387-94 Level IV rated capacity of less than valve x10-4 |
Dimensions and weight of electric three-way regulating valve
Public diameter DN |
25 |
32 |
40 |
50 |
65 |
80 |
100 |
125 |
150 |
200 |
250 |
300 |
|
L |
PN16 |
185 |
200 |
220 |
250 |
275 |
300 |
350 |
410 |
450 |
550 |
670 |
770 |
PN40 |
190 |
210 |
230 |
255 |
285 |
310 |
355 |
425 |
460 |
560 |
740 |
803 |
|
PN64 |
200 |
200 |
240 |
265 |
295 |
320 |
370 |
440 |
475 |
570 |
752 |
819 |
|
H1 |
135 |
152 |
165 |
180 |
200 |
220 |
222 |
265 |
322 |
362 |
508 |
563 |
|
A |
225 |
310 |
|||||||||||
H room temperature |
555 |
561 |
660 |
675 |
863 |
868 |
872 |
905 |
920 |
950 |
1203 |
1265 |
|
H medium temperature type |
707 |
709 |
812 |
827 |
1027 |
1032 |
1036 |
1120 |
1135 |
1165 |
1485 |
1557 |
|
weight (PN64 at room temperature) |
50 |
55 |
70 |
78 |
110 |
120 |
150 |
180 |
310 |
410 |
650 |
810 |