1、 Product functions and features
wEquipped with automatic zero stabilization function
wEquipped with digital tuning function
wEquipped with power-off memory function
wStrong anti electromagnetic interference capability
wHas multiple wiring methods
wEquipped with automatic fault diagnosis function
wEquipped with programmable state setting function
wHas high measurement accuracy
2、 Main general technical indicators
1Measurement line system and power consumption:
Can measure the total phase voltage of a three-phase four wire circuit or any other standard/Line voltage(V)Current(I)Power consumption
(PTheQTheS)Electric energy(WhTheQh)Power factor(PF)Frequency(F)Zero sequence current(IO)Wait, wait34A parameter.
2Working voltage:
AC85~265V 40~70Hz,DC85~330V(Standard)
DC18~90V(optional)
3Power consumption of the whole machine:≤4VA
4Overload capacity:
Voltage:750VContinuous;1000V 10Seconds;1200V 3second
electric current:2Multiple rated continuous;20Double rated1second
5Input Range:
U:5~120V/600V(Maximum)600V)Automatic range switching
I:0~
6Absorption power consumption:
Voltage: <0.8VA/400V,<0.25VA/220V
Current: <0.1VA/
7Accuracy
|
voltageVx |
0.2%RD~0.5%RD |
|
currentIxx |
0.2%RD~0.5%RD |
|
active powerP |
0.5%RD |
|
reactive powerQ |
0.5%RD |
|
apparent powerS |
0.5%RD |
|
power factorPF |
0.5%RG |
|
active energyWh |
0.5%RD |
|
Reactive energyQh |
1.0%RD |
|
zero-sequence currentIO |
1%RG |
|
frequencyHz |
0.2%RG |
8Programmable design:
Programming mode: (password)
Measurement system selection: three-phase four wire/three-phase three-wire/One phase, two lines/One phase, three lines/three-phase balance
CT,PTTransformation ratio:1~59999
Communication:
☆Baud rate1200/2400/4800/9600
☆Data bit:8or7
☆Checkpoint: Odd/by chance/No checksum
☆Stop position:1or2
☆Communication protocol:Modbus RTU / MODBUS ASCII rs- 485 / RS
☆Clock: Year, Month, Day, Hour, Minute, Second, Week
☆Clock error:0.5second/24hour
☆Electric energy accumulation reset: (password)
☆Calibration: (Password)
9Insulation strength:
Object: In input/output/Between power sources
Reference standard:IEC688-1992
Test method:AC2KV 1minute leakage current2mA
10Electromagnetic compatibility:
①Surge(1.2/50-8/20uS)
Object: Power supplyI/0line
Reference standard:IEC61000-4-5/IEC61000-4-11
Test method:4KV(1.2×50uS)
②Fast transient pulse train
Object: Power supplyI/0line
Reference standard:IEC61000-4-4
Test method: Power supply:4KV 2.5KHz
I/0Line:2KV 5KHz
③Electrostatic Discharge
Object: Power supplyI/0line
Reference standard:IEC61000-4-2
Contact discharge:6KV
Air gap discharge:8KV
④radiofrequency electromagnetic fields
Object: Device itself
Reference standard:IEC61000-4-3
Test method:10V/mModerate intensity electromagnetic radiation (such as distance not less than
⑤stability
Temperature range: -10~+
Temperature impact:10ppm/℃
Long term stability:<0.2%year
11Isolation:
input/output/Mutual isolation between power sources
3、 General instructions
◆Structure: Front wiring of the board
◆Installation method:
◆Shell material: flame retardant plastic (all black)
◆Overall dimensions: