MS7043T Isolation Distributor
1、 Characteristics
·1 in 2 out
·Capable of providing power distribution through the transmitter
·4-20mA input
·The first output is 4-20mA (supporting output circuit power supply)
·Second output DC current or voltage signal
2、 Technical specifications
·Provide isolated DC power supply to the transmitter on site, and receive 4-20mA current signal input from the transmitter. After isolation, interference suppression and other processing, the 4-20mA signal is divided into two signal outputs. The first output is 4-20mA, and the second output is 4-20mA or 1-5V. ·DC power supply mode, the first output of the instrument is loop power supply, and the power supply - input - output channels are isolated from each other. ·Standard 35mm DIN rail card installation. The wiring plug terminals for broadcasting can be connected by spring compression. ● Input Input signal: 4~20mA Input impedance: 24 Ω Power distribution for transmitter: When 20mA, ≥ 18V (factory default), if larger power distribution is required (such as ≥ 22V), please specify when ordering Maximum input current: approximately 24mA ● Output First output Output current (lo): 4-20mA Output circuit power supply voltage (Ue): 12-35V Voltage drop (Ud): 3V Output load resistance (RL): Calculation formula RL ≤ (Ue Ud) ÷ 0.02(Note: The selection of power supply voltage for the output circuit should be determined based on the size of the load. Overvoltage and low load will exacerbate the heating condition of the isolator.) |
Second output Output current: 4-20mA; 0-20mA; Or specify the current range Output voltage: 1-5V; 0~5V; Other specified voltages Load resistance: When outputting 4-20mA, ≤ 550Q (factory default) When outputting 1-5V, ≥ 100K Ω voltage Output load: When outputting 1 (0)~5V, ≥ 10KQ Output ripple:<10mVp-p ● Power supply Power supply voltage range: 20~30VDC Rated supply voltage: 24VDC Current consumption (when powered by 24VDC):<60mA ● Comprehensive parameters Standard accuracy: ± 0.1% Temperature drift: ± 0.015%/℃ Response time:<10ms Isolation capability: 2.5KV, 1min.50Hz between input output power supply Insulation resistance: ≥ 100MQ/500VDC between input output power supply Working environment temperature: -20-+60 ℃ Storage environment temperature: -40~+80 ℃ Shell material/protection level: PC (polycarbonate) material/IP20 Dimensions: 16 × 116 × 110 (mm) |
3、 Model selection
4、 Dimensions and installation diagram
● Installation
1.35mm standard DIN rail card installation. Please pay attention to the stability and firmness of the card position during installation.
2. Install vertically as much as possible to facilitate heat dissipation inside the instrument.
● Typical applications
1. Used to provide distribution voltage to on-site transmitters and isolate and convert input signals.
2. Devices connected to the site: Active electrical signals from two-wire or three wire non smart transmitters.
3. Connect to the control system (or other unit combination instruments): The AI card of each DCS/PLC receives current or voltage signals.
● External dimensions
Width (thickness) x height x depth=16 x 116 x 110 (mm)
6、 Terminal wiring diagram
Terminal wiring: Plug and unplug terminal blocks, connected by self boosting spring type compression. The cross-sectional area of the wire shall not exceed 2.5mm2Multiple bundles or single stranded cables.