VIP member
KG-L type water purifier
Product details (1) Design parameter table Surface load rate 7.5-10.0m3/h.m2 Raw water turbidity suitable for 50-500mg/l Filter effluent turbidity<5mg
Product details
product details
(1) Design parameter table
surface loading rate
|
7.5-10.0m3/h.m2
|
Raw water turbidity
|
Suitable for 50-500mg/l
|
Filter effluent turbidity
|
<5mg/l
|
Overload coefficient
|
β=1.3
|
Filtration speed
|
V=10m/h
|
Flushing intensity
|
14L/m2.s
|
Rinse time
|
4-6min
|
Total residence time
|
40 min
|
The sludge discharge cycle and backwash cycle should be determined during commissioning based on the different turbidity of the raw water.
|
(2) Grading Table of Filter Media
Product Name
|
specifications
|
floor height
|
White coal
|
1.2-1.6mm
|
400mm
|
Quartz sand
|
0.5-1.2mm
|
450mm
|
pebble
|
2-4mm
|
75mm
|
pebble
|
4-8mm
|
75mm
|
pebble
|
8-16mm
|
100mm
|
pebble
|
16-32mm
|
270mm
|
(3) List of Dimensions and Connections of Water Purifiers
water yield
Code name
|
5
|
10
|
15
|
20
|
30
|
40
|
50
|
60
|
100
|
a
|
1500
|
2000
|
2500
|
3000
|
4000
|
4800
|
5800
|
6200
|
9000
|
b
|
1200
|
1500
|
1600
|
2000
|
2200
|
2300
|
2400
|
2500
|
2800
|
DN1
|
50
|
80
|
80
|
100
|
100
|
100
|
150
|
150
|
200
|
DN2
|
50
|
80
|
80
|
100
|
100
|
100
|
150
|
150
|
200
|
DN3
|
100
|
150
|
150
|
200
|
200
|
200
|
250
|
250
|
300
|
DN4
|
100
|
150
|
150
|
200
|
200
|
200
|
250
|
250
|
300
|
DN5
|
25
|
25
|
25
|
25
|
50
|
50
|
50
|
50
|
80
|
h1
|
0.22
|
0.22
|
0.25
|
0.25
|
0.26
|
0.26
|
0.27
|
0.30
|
0.35
|
h2
|
0.42
|
0.42
|
0.46
|
0.46
|
0.46
|
0.46
|
0.53
|
0.55
|
0.61
|
h3
|
0.22
|
0.25
|
0.25
|
0.25
|
0.29
|
0.29
|
0.30
|
0.30
|
0.35
|
h4
|
0.50
|
0.70
|
0.70
|
0.70
|
0.70
|
0.70
|
0.70
|
0.70
|
0.70
|
h5
|
0.13
|
0.13
|
0.13
|
0.13
|
0.14
|
0.14
|
0.14
|
0.14
|
0.14
|
L1
|
100
|
100
|
100
|
100
|
130
|
130
|
130
|
130
|
130
|
L2
|
100
|
100
|
100
|
100
|
130
|
130
|
130
|
130
|
130
|
L3
|
500
|
500
|
500
|
500
|
600
|
600
|
600
|
600
|
600
|
Operating weight T
|
8
|
13
|
18
|
24
|
34
|
41
|
55
|
62
|
100
|
Explanation: 1. The dimensions in the chart are in millimeters, and the elevation (h) is in meters;
2. For models with a water production rate of 20T/h or above, please use reinforced concrete structure for the foundation. The specific foundation dimensions will be determined based on the actual situation;
3. The external structure and the orientation of the inlet and outlet pipes can be designed and manufactured separately according to the actual situation.
Online inquiry