1、 Overview
The FT35-11 ventilation fan can be used for general factory, warehouse, office, and residential ventilation or to enhance heating and heat dissipation. If the casing is removed, it can be used as a free fan. It can also be installed in series at intervals in longer exhaust pipes to increase the air pressure in the pipes.
This series of products adopts a direct connection structure where the impeller is directly mounted on the motor shaft. Under the condition that the circumferential speed of the impeller does not exceed 60 meters per second, three speeds are provided: 2900, 1450, and 960 revolutions per minute. The impeller rotates counterclockwise when facing the air inlet direction.
The gas passing through the fan should be non corrosive and free of significant dust, and its temperature should not exceed 60 ℃.
This fan is mainly composed of three parts: impeller, casing, and collector.
2、 Anti corrosion purpose
This series of fans has the advantages of good corrosion resistance, light weight, high specific strength, resistance to aging, simple structure, and easy use. It is suitable for emitting corrosive gases of a certain concentration and is an ideal equipment for ventilation. Its series form is the addition of "F", i.e. "FT35" form, where "F" represents "anti-corrosion".
3、 Performance parameter table of FT35-11 fiberglass axial flow fan
The parameters provided in the performance table, unless otherwise specified, are calculated based on the standard inlet state of the fan, which is the standard state of air medium, pressure of 101325Pa, temperature of 20 ℃, density of 1.2kg/m3, and relative humidity of 50%.