main features
The EDA9083 analog input, frequency measurement, and counting module can measure: 8 voltage or current input signals, and 2 frequency or pulse counting input signals.
The EDA9083 module can be widely used in various industrial control and measurement systems. It can measure the true effective value of AC or DC voltage signals ranging from 0 to 250V or current signals ranging from 0 to 200mA; Measure power frequency, flow measurement, transmitter pulse output measurement, etc. Its output is in 485 bus mode. Dual protocol: ASCII code protocol and hexadecimal LC-04 protocol, its ASCII code instruction set is compatible with modules such as NuDAM and ADAM, and can be hung on the same 485 bus as control modules from other manufacturers for easy computer programming.
major function
●Analog input:
8 channels with voltage ranging from 0 to 250V. The input signal is DC or AC (frequency 25-75Hz).
The range options are: 100mV, 200mV, 500mV, 1V, 2V, 5V, 10V, 20V, 60V, 100V, 200V, 250V Or 8 channels of 0-20mA current. The input signal is DC or AC (frequency 25-75Hz).
The range options are: 1mA, 10mA, 20mA, 100mA, 200mA.
Signal processing: 16 bit A/D sampling; Sampling rate: 3000 samples per second. Output true valid value.
Measurement cycle: 0.2 seconds per channel, 8-channel cyclic measurement.
Overload capacity: 1.2 times the range can be measured correctly; Overload twice the range input for 1 second without damage.
●Frequency measurement and counting input:
Two independent optoelectronic isolation inputs; Simultaneously measure and count the frequency of the input signal;
When applied to counting: pulse width>100 uS, signal high level 5V -30V. Maximum count value: FFFFFFFFH。
2-channel pulse counting input can be set to power down storage or power down no storage; The count value is not stored after power failure, and accumulates from 0 after power on; The count value is stored during power failure, and the count value during power failure is stored in EEPROM. After power on, it accumulates from the value before power failure.
When used for frequency measurement: the frequency range is 0.1Hz to -3 KHz, and the input voltage range is 5-30V.
●Isolation: Isolation between analog signal input, frequency measurement and counting input, and communication interface output, with an isolation voltage of 1000V DC. SLT, DATA+, DATA -, VCC, GND are output terminals and are grounded together with the GND terminal; The common ground terminal for the 8-channel measurement signal input is the AGND terminal;
●Communication output
Interface: RS-485 interface, two-wire system, ± 15KV ESD protection.
Protocol: Dual protocol: ASCII code protocol and hexadecimal LC-04 protocol. Choose between suspended or grounded by SLT.
Speed: 1200, 2400, 4800, 9600, 19200 Bps, software adjustable.
Module address: 00~FF can be set by software.
●Measurement accuracy: 0.2 level or higher.
●Module power supply:+ 8-30V DC * Power consumption: Typical current consumption is 50 mA.
●Working environment: Working temperature: -20 ℃~70 ℃; Storage temperature: -40 ℃~85 ℃; Relative humidity: -5% to 95% without condensation.
●Installation method: DIN rail card mounting volume: 122mm * 70mm * 43mm. Return