overview
■ Model and its meaning
■ Application
-The dual delay time relay can set 2 sets of power on delay time, which can be used for heavy load time-sharing input to prevent the main circuit from being affected
The peak current is too high.
-Specific application scenarios can replace two time relays, saving costs.
■ Characteristics
-Two sets of power on delay settings can be set separately.
-Ultra wide delay range, adjustable from 0.1 seconds to 10 days (10 levels).
-Available in AC/DC 12V-240V ultra wide operating voltage specifications.
-The working status of the relay is indicated by LED indicator lights.
-Ultra small size, only 18mm width, 35mm card rail installation.
Main technical parameters
GRT8-2T | |
function | Dual setting power on delay |
power terminal | A1-A2 |
Rated control power supply voltage | AC/DC 12-240V(50-60Hz) |
Power consumption | AC 0.09-3VA/DC 0.05-1.7W |
Rated control power supply voltage | AC 220V(50-60Hz) |
Power consumption | AC max.6VA/1.9W |
Allowable fluctuation range of power supply | -15%;+ 10% |
Power indicator light | Green LED |
Delay range | 0.1 seconds to 10 days, normally open, normally closed |
Setting method | knob |
Setting accuracy | 10% |
repeatability | 0.2% |
Temperature fluctuation error | 0.05%/℃,at=20℃(0.05%℉,at=68℉) |
Output contact parameters | 2 sets of conversion contacts |
16A/ AC1 | |
250VAC/24VDC | |
Minimum switching power | 500mW |
Output relay indication | red led |
mechanical life | 1×10 |
Electrical lifespan (resistive load) | 1×10 5 |
Reset time | Maximum 200ms |
Ambient Temperature | -20℃ ~ +55℃ |
Storage and transportation environment temperature | -35℃ ~ +75℃ |
Installation method | 35mm card rail installation |
protection grade | IP20 |
Installation position | arbitrary |
Installation altitude | ≤ 2000 meters |
pollution degree | 2 |
Wiring ability | 1 × 2.5mm or 2 × 1.5mm |
External dimensions | 90mm×18mm×64mm |
weight | W240- 82g,A230-82g |
Compliant with standards | GB14048.5,IEC60947-5-1,EN 61812-1 |
Wiring diagram
function diagram
Appearance and size installation