Sichuan Deyang Deyi Electronic Instrument Co., Ltd
Home>Products>DY-PEW wireless inspection device
Product Groups
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
  • Address
    No. 123, Section 3, Tianshan South Road, Jingyang District, Deyang City
Contact Now
DY-PEW wireless inspection device
The wireless inspection device has wiring simulation function and can measure three-phase three wire and three-phase four wire current imbalance. Quic
Product details
product overview

The wireless inspection device has wiring simulation function and can measure three-phase three wire and three-phase four wire current imbalance. Quickly identify hidden faults, power theft, leakage and other abnormal situations. This instrument is a powerful assistant for conducting power inspection work.

Functional Features

Adopting industrial grade TFT large color screen, each function of the instrument is displayed on one screen, making it easy for users to see at a glance when using.

Simultaneously measure multiple electrical parameters such as energy error, voltage, current, power, phase, frequency, etc., and display vector diagrams and line checking results.

Optional 5A, 100A, 500A, 1000A clamp gauges can be used to directly measure the transformation ratio of low-voltage current transformers.

Real time measurement of 2-21st harmonic and waveform of A, B, and C three-phase voltage and current, to timely understand the power supply quality of the power grid.

Equipped with a USB interface, it can connect to a USB flash drive, creating a super large space for easy data copying.

Technical Parameter

INPUT VOLTAGE

Measurement range: 30V~480V, measurement accuracy: ± 0.05%/± 0.1%

Input Current

Built in CT measurement range: 0.2-5A, measurement accuracy: ± 0.05%/± 0.1%

Clamp CT measurement range: 5A, 100A, 500A, 1000A, measurement accuracy: ± 0.1%/± 0.2%/± 0.5%

input frequency

Measurement range: 45-55Hz, measurement accuracy: ± 0.01Hz

phase measurement

Measurement range: -180 ° to+180 °, measurement accuracy: ± 0.05 °/± 0.1 °

harmonic measurement

Measurement range: 2-21 times, measurement accuracy: ± 0.05%

Electric energy, power

Accuracy of active power measurement: ± 0.05%/± 0.1%, accuracy of reactive power measurement: ± 0.2%

Working power supply

AC 55V~260V