VIP member
DDSK1122S-Z 2-level single-phase electronic cost controlled energy meter
Main features: The single-phase electronic cost controlled energy meter is used to measure single-phase active energy with a rated voltage of 220V and
Product details
Technical parameters:
Rated voltage (Un) |
220V |
|
Operating Voltage |
0.9Un~1.1Un |
|
Expand working voltage |
0.8Un~1.15Un |
|
Current specifications |
5(60)A |
|
Rated frequency |
50Hz |
|
Clock accuracy (daily error) |
0.5S/d(23℃) |
|
accuracy class |
Active Level 2 |
|
operation temperature |
-25℃~+55℃ |
|
working temperature limit |
-45℃~+75℃ |
|
power consumption | Non communication state ≤ 1.5W, 6VA; Communication status ≤ 3W | |
reliability | ≥ 15 years | |
External dimensions | Length x Width x Thickness: 160mm x 118mm x 71mm |
Online inquiry