1、 Introduction to Carbon Monoxide Detection Transmitter
The BYC100-CO carbon monoxide detection transmitter is a device developed and produced by Shenzhen Boyunchuang Environmental Technology Co., Ltd. for indoor air quality. It is mainly used to measure the content of CO gas in indoor air, provide effective CO concentration data, remind users to take safety measures, and drive the linkage of the fresh air system, providing users with a comfortable home environment. The product adopts original imported electrochemical sensors and computing chips, which have the characteristics of high precision, high resolution, and good stability. Widely used in building HVAC, building energy conservation, smart homes, underground garages, airport stations and other places.
2、 Introduction to Carbon Monoxide Detection Transmitter Gas
Carbon monoxide (CO) is a product of incomplete combustion of carbon containing substances such as coal and petroleum. It is a colorless, odorless, and non irritating toxic gas that is almost insoluble in water and difficult to react chemically with other substances in the air. Therefore, it can remain in the atmosphere for 2-3 years. If there is severe local pollution, it poses a certain risk to the health of the population.
3、 Characteristics of carbon monoxide detection transmitter
1. Stable and reliable communication, wide range power supply DC12-24V;
2. Comprehensive anti reverse, overvoltage, overcurrent, and inter line protection capabilities;
3. Carefully designed circuit software and hardware, with low failure rate and short stability time;
4. Original imported electrochemical sensors and professional grade signal processing chips ensure the accuracy of sensor data;
5. The structure takes into account aerodynamic principles to achieve automatic real-time sampling, which can be used for a long time;
6. The measurable environmental parameters cover a wide range and can meet various detection environment requirements;
7. Output 4-20mA, 0-10V, RS485 and other signals for easy use.
4、 Carbon monoxide gas content standard
5、 Technical parameters of carbon monoxide detection transmitter
4、 Carbon monoxide gas content standard
Content of CO in the air | Inhalation time and symptoms of poisoning display |
100ppm | The maximum amount allowed for adults to be present in it |
200ppm | After 2-3 hours, there will be mild headaches, dizziness, and nausea |
400ppm | Frontal pain within 2 hours, life-threatening after 3 hours |
800ppm | Headache and nausea within 45 minutes, death within (2-3) hours |
1600ppm | Headache and nausea within 20 minutes, death within 1 hour |
5、 Technical parameters of carbon monoxide detection transmitter
Technical Parameter | BYC100-CO |
Detect gas | carbon monoxide(CO) |
Detection Principle | electrochemistryDetection Principle |
measuring range | 0~500ppm 0~1000ppm |
resolution | 1ppm |
accuracy | ≤±5%F.S |
Warm-up time | 30S |
sampling interval | 3S |
response time(T90) | <1minute |
service life | 5Years and above |
zero drift | <±2% |
Nonlinear | <1%F.S |
repeatability | ±2% |
Supply Voltage | DC 12~24V |
signal output | 4~20mA 0~10VRS485 modbus RTU |
work environment | -10~50℃; 0-95% RH (no condensation) |
Environment | -30~60℃; 0-100% RH (no condensation) |
Shell material | Plastic ABS |
protection grade | IP30 |
Installation method | Wall mounted and ceiling mounted |
Weight/Size | 120g/ 110mm×70mm×38mm |
notes |
6、 Installation of carbon monoxide detection transmitter size
1. First, fix the installation disk on the wall
2. After connecting the equipment, fix it on the installation disk.
3. Do not connect the transmitter to a voltage higher than 24VDC. To prevent excessive voltage from burning out the sensor.
4. Install the transmitter at the location that needs to be tested, away from the heating element or steam source, and prevent direct sunlight.