VIP member
Capacitive RF admittance level gauge
Capacitive RF admittance level gauge is a universal level gauge used for continuous level measurement. The product is applied in industrial and mining
Product details
Capacitive RF admittance level gaugeAs a universal level gauge used for continuous level measurement, the product is applied in industrial and mining sites and is suitable for most applications. The instrument consists of a circuit unit, an explosion-proof housing, and rod or cable type sensing elements. There are multiple types of sensors to choose from, and the instrument can be installed as a whole or separately.

Typical applications of capacitive RF admittance level gauge:
Conductive and insulating liquids - chemical, oilfield, water and sewage treatment
Conductive and insulating liquids - papermaking, pharmaceuticals, water and wastewater treatment
Powder: ash, powder - power plants, metallurgy, cement
Particles: coal, grain - power plants, metallurgy, grain
Features of Capacitive RF Admittance Level Gauge:
Strong universality: applicable to various occasions, including fly ash, particles, powders, liquids, viscous, conductive and non-conductive materials.
Anti adhesive circuit: The use of anti adhesive electronic circuits can eliminate false signals caused by material adhesion.
Detachable probe: The probe and controller can be separated, and the gold-plated contact pins are connected. Installation and removal do not affect feeding and discharging.
Probe resistant to high and low temperatures: The probe is suitable for working environments ranging from -80 ℃ to 180 ℃ and also offers a rod type design; Flat ceramic high-temperature probe (temperature resistance of 800 degrees).
Large output capacity: It adopts a relay contact output with a capacity of 2A and 220Vac, and has a status light to display the working status with a delay function of 0-30 seconds.
SMT technology: makes electronic circuits more resistant to vibration, with more stable and reliable circuit parameters.
Wave pressure technology: increases the usage pressure of the probe.
Warranty period: The warranty period is 3 years.

Technical parameters of capacitive RF admittance level gauge
Relay capacity: DPDT, rated 2A, 220Vac or 1.5A, 28VDC
Delay: 0-30 seconds continuously adjustable
Power supply: 220Vac or 24V/DC
Power: 3W
Sensitivity: 0.3pF-800pF
Material temperature: -80 ℃ to 180 ℃ (high-temperature probes can be used for temperatures above 180 ℃)
Circuit temperature resistance: -40 ℃ to 66 ℃.